Drive IsolationStock of Drive isolation transformers, Toronto warehouse.Drive isolation transformer reduces the harmonic distortion, attenuates electrical noise, and diminishes line voltage notching caused by motor drives. The addition of the inductive reactance from a transformer to the motor drives power source effectively reduces the notching effects it has on the power to other loads. In three phase applications, drive isolation transformers reduce harmonic distortion by eliminating the triple harmonics (when the transformer is connected delta-wye). The harmonics produced by the motor drive are trapped in the delta primary of the transformer. The transformer must be K-rated to handle the heat generated by the trapped harmonics in the primary. A reduction in harmonic distortion improves the power factor and reduces the harmonic effect on other loads. Attenuation of electrical noise due to ground currents is achieved by isolation and shielding. The secondary, of drive isolation transformer is isolated from the primary providing a good amount of noise attenuation. Multiple shielded drive isolation transformers provide excellent noise attenuation needed to prevent data disruption in digital electronic equipment. Please choose Aluminum or Copper winding. Drive Isolation Transformers Features:
|